Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-401a 28 2.3.11
GP Dimming Panels
GRAFIK Systems
®
SL
1
DL
2
SL
2
DL
3
SL
3
DL
1
L
1
L
2
L
3
GP3 Mini Panel Wiring Overview
220-240 V
Wiring Tips
Wire the GP3 similar to wiring a lighting
Distribution Panel:
•Runfeedandloadwiring.Nootherwiringor
assembly required.
•CommonNeutralsarenotpermitted.Run
separate Neutrals for each load circuit.
The GP3 can provide temporary lighting:
•Wireallloads.
•Donotremovethebypassjumpersthatprotect
the Dimming Modules.
•UseBranchCircuitBreakerstoswitchlightson
and off.
Power Feed
(Hot/Live)
TerminalBlock
Neutral Feed
Load
Branch
Circuit
Breakers
DimmedHot/Live
Load Neutral
Bypass Jumpers -
Do Not Remove
Typical Load Circuit
Ground
Wire Sizes
•PowerFeed:
18 AWG (1.0 mm
2
)to4AWG(25.0mm
2
)
•NeutralFeed:
14 AWG (2.0 mm
2
) to 6 AWG (10.0 mm
2
)
•DimmedHot/Live:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
•LoadNeutral:
14 AWG (2.0 mm
2
) to 6 AWG (10.0 mm
2
)
NEC® Class 2/
PELV Wiring
Power Equipment