Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-401a 31 2.3.11
GP Dimming Panels
GRAFIK Systems
®
GP4 Mini Panel Wiring Overview
220-240 V
Wiring Tips
Wire the GP4 similar to wiring a lighting
Distribution Panel:
•Runfeedandloadwiring.Nootherwiringor
assembly required.
•CommonNeutralsarenotpermitted.Run
separate Neutrals for each load circuit.
The GP4 can provide temporary lighting:
•Wireallloads.
•Donotremovethebypassjumpersthat
protect the Dimming Modules.
Wire Sizes
•PowerFeed:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
•NeutralFeed:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
•DimmedHot/Live:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
•LoadNeutral:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
DH
1
SH
1
H
1
N
1
N
1
DH
2
SH
2
H
2
N
2
N
2
Power Feed
(Hot/Live)
TerminalBlock
Load
DimmedHot/Live
Bypass Jumpers
Do Not Remove
Typical Dimming Leg
Load Neutral
Neutral Feed
Ground
NEC® Class 2/
PELV Wiring
Power Equipment