Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-401a 32 2.3.11
GP Dimming Panels
GRAFIK Systems
®
Feed Wiring
Terminal
Block
Load Neutral
Load
DimmedHot/Live
Branch
Circuit
Breakers
NEC® Class 2/
PELV wiring
Neutral Feed
Power Feed
(Hot/Live)
Bypass
Jumpers -
Do Not
Remove
Typical Load Circuit
GP8-24 Standard-Size Panel Wiring Overview
Wiring Tips
Wire the GP8-24 similar to wiring a lighting
Distribution Panel:
•Runfeedandloadwiring.Nootherwiring
or assembly required.
•CommonNeutralsarenotpermitted.Run
separate Neutrals for each load circuit.
The GP8-24 can provide temporary lighting:
•Wireallloads.
•Donotremovethebypassjumpersthat
protect the Dimming Modules.
•UseBranchCircuitBreakerstoswitchlights
on and off.
Wire Sizes
•PowerFeedStandardMainLugs
14 AWG (2.0 mm
2
) to 2/0 AWG (70.0 mm
2
)
•PowerFeedDualTapMainLugs
6 AWG (10.0 mm
2
) to 4/0 AWG (120 mm
2
)
•NeutralFeed:
6 AWG (10.0 mm
2
)to350MCM(177.0mm
2
)
•DimmedHot/Live:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
•LoadNeutral:
14 AWG (2.0 mm
2
) to 6 AWG (10.0 mm
2
)
Power Equipment